Disability Access Audit Progress Report Building Floor/ Issue Recommendation Progress Area Hyde Hospital Ground Non Disability Discrimination Act Provide two work surface heights (dual height worktops) to Complete (Older Peoples Floor (DDA) Compliant - A lowered section is accommodate customers or visitors standing and sitting (including Service) not provided to the reception counter wheelchair users), as appropriate to the circumstance Refer to to allow approach by all potential users BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop both seated and standing. or other form of hearing enhancement system. Refer to BS8300:2001 Section 9.3.2) Hyde Hospital Ground Non DDA compliant Toilet in Provide a lavatory suitable for use by ambulant people adjacent to Complete (Memory Clinic) Floor Outpatient waiting area – Must provide waiting area. Refer to BS8300:2001 Redecorate walls to highlight sanitary fittings and aids, such as toilet fittings or alternatively colour contrasting bands (stickers) could be seats and grab rails that contrast in used as an interim measure to highlight the fittings, Refer to terms of colour and luminance with BS8300:2001 background wall and floor finishes. Refer to BS8300:2001 Section 12.4.11 Hyde Hospital Ground Non DDA compliant door access - Adjust door closer to provide 20N maximum resistance. Refer to Complete (Main Entrance) Floor Excessive force (over 20N) required ...

Informations

Publié par
Nombre de lectures 16
Langue English

Extrait

Disability Access Audit Progress Report
Building
Floor/
Area
Issue
Recommendation
Progress
Hyde Hospital
(Older Peoples
Service)
Ground
Floor
Non Disability Discrimination Act
(DDA) Compliant - A lowered section is
not provided to the reception counter
to allow approach by all potential users
both seated and standing.
Provide two work surface heights (dual height worktops) to
accommodate customers or visitors standing and sitting (including
wheelchair users), as appropriate to the circumstance Refer to
BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop
or other form of hearing enhancement system. Refer to BS8300:2001
Section 9.3.2)
Complete
Hyde Hospital
(Memory Clinic)
Ground
Floor
Non DDA compliant Toilet in
Outpatient waiting area – Must provide
sanitary fittings and aids, such as toilet
seats and grab rails that contrast in
terms of colour and luminance with
background wall and floor finishes.
Refer to BS8300:2001 Section 12.4.11
Provide a lavatory suitable for use by ambulant people adjacent to
waiting area. Refer to BS8300:2001 Redecorate walls to highlight
fittings or alternatively colour contrasting bands (stickers) could be
used as an interim measure to highlight the fittings, Refer to
BS8300:2001
Complete
Hyde Hospital
(Main Entrance)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Tameside
(Outpatients
Department’)
First Floor
Non DDA compliant Toilet in
Outpatient waiting area – Must
provide sanitary fittings and aids, such
as toilet seats and grab rails that
contrast in terms of colour and
luminance with background wall and
floor finishes. Refer to BS8300:2001
Section 12.4.11
Create DDA Complaint toilet area adjacent to waiting area - Provide a
lavatory suitable for use by ambulant people adjacent to waiting area.
Refer to BS8300:2001 Redecorate walls to highlight fittings or
alternatively colour contrasting bands (stickers) could be used as an
interim measure to highlight the fittings, Refer to BS8300:2001
Complete
Last updated:
October 2008
Tameside
(Outpatients
Department)
First Floor
Non DDA Compliant - A lowered
section is not provided to the reception
counter to allow approach by all
potential users both seated and
standing.
Provide two work surface heights (dual height worktops) to
accommodate customers or visitors standing and sitting (including
wheelchair users), as appropriate to the circumstance Refer to
BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop
or other form of hearing enhancement system. Refer to BS8300:2001
Section 9.3.2)
Complete
Rochdale
(Sudden
Resource
Centre )
Ground
Floor
Non DDA compliant Toilet in Clinic
waiting area – Must provide sanitary
fittings and aids, such as toilet seats
and grab rails that contrast in terms of
colour and luminance with background
wall and floor finishes. Refer to
BS8300:2001 Section 12.4.11
Create DDA Complaint toilet area - Provide a lavatory suitable for use
by ambulant people adjacent to waiting area. Refer to BS8300:2001
Redecorate walls to highlight fittings or alternatively colour contrasting
bands (stickers) could be used as an interim measure to highlight the
fittings, Refer to BS8300:2001
Complete
Rochdale
Hospital
(Birch Hill )
External
Carpark
A designated setting-down
point/accessible parking bay is not
provided close to the principal
entrance of the building.
Provide a designated setting-down point/accessible parking bay
suitable for disabled passengers on firm and level ground, close to the
principal or alternative, accessible entrance to a building. Refer to
BS8300:2001 Section 4.2
Complete
Rochdale
Hospital
(Birch Hill –
Beach Ward)
Ground
Floor
(Beach
Ward)
A Stepped Exit Only Route
Provide level egress in the form of a ramp – Means of Escape
Complete
Rochdale
Hospital
(Birch Hill –
Beach & Hazel
Wards)
Ground
Floor
Upgrade existing handrails
Upgrade handrails to comply with BS8300:2001 section 5.8.5
(Reduced Ligature Handrails installed)
Complete
Rochdale
Hospital’
(Birch Hill –
Administration
Block)
Ground
Floor
Non DDA compliant door access -
Fit power assisted automatic swing doors
Complete
Rochdale
Hospital
(Birch Hill –
Beach Ward)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors)
Complete
Fairfield
Hospital, Bury
Ground
Floor
Does not comply with Approved
Document M of the Building
Upgrade facility to comply with BS8300:2001 Section 12
Complete
Last updated:
October 2008
(Roch House)
Regulations/BS8300:2001
Fairfield
Hospital, Bury
(Roch House)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Fairfield
Hospital, Bury
(Ward 31)
First Floor
Non DDA Compliant - A lowered
section is not provided to the reception
counter to allow approach by all
potential users both seated and
standing.
Provide two work surface heights (dual height worktops) to
accommodate customers or visitors standing and sitting (including
wheelchair users), as appropriate to the circumstance Refer to
BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop
or other form of hearing enhancement system. Refer to BS8300:2001
Section 9.3.2)
Complete
Fairfield
Hospital, Bury
(Pennine
House)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Lee’s Street
Clinic
(Tameside)
External
Carpark
A designated setting-down
point/accessible parking bay is not
provided close to the principal
entrance of the building.
Provide a designated setting-down point/accessible parking bay
suitable for disabled passengers on firm and level ground, close to the
principal or alternative, accessible entrance to a building. Refer to
BS8300:2001 Section 4.2
Complete
Lee’s Street
Clinic
(Tameside)
Ground
Floor
Non DDA Compliant counter - A
lowered section is not provided to the
reception counter to allow approach by
all potential users both seated and
standing.
Provide two work surface heights to accommodate customers or
visitors standing and sitting (including wheelchair users), as
appropriate to the circumstance Refer to BS8300:2001 Section
11.1.3/6 & figure 33 (& Provide an induction loop or other form of
hearing enhancement system. Refer to BS8300:2001 Section 9.3.2)
Complete
Lee’s Street
Clinic
(Tameside)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Royal Oldham
Hospital:
Parklands
House
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Royal Oldham
Hospital:
Parklands
House
Ground
Floor
Non DDA Compliant Cashier Counter -
A lowered section is not provided to
the reception counter to allow
approach by all potential users both
Provide two work surface heights (dual height worktops) to
accommodate customers or visitors standing and sitting (including
wheelchair users), as appropriate to the circumstance Refer to
BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop
Complete
Last updated:
October 2008
seated and standing.
or other form of hearing enhancement system. Refer to BS8300:2001
Section 9.3.2)
Royal Oldham
Hospital: Forest
House
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Royal Oldham
Hospital:
Cherrywood
House
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Royal Oldham
Hospital:
Cherrywood
(Refections)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Royal Oldham
Hospital:
Orchard House
(Royton)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Houghton
House
(Stamford
Street)
External
Carpark
A designated setting-down
point/accessible parking bay is not
provided close to the principal
entrance of the building.
Provide a designated setting-down point/accessible parking bay
suitable for disabled passengers on firm and level ground, close to the
principal or alternative, accessible entrance to a building. Refer to
BS8300:2001 Section 4.2
Complete
Houghton
House
(Stamford
Street)
External
Carpark
Non DDA Compliant - Stepped exit
only route
Provide level egress in the form of a ramp – Means of Escape
Complete
Certek House
(Rehabilitation
Clinic)
Ground
Floor
Non DDA Compliant - A lowered
section is not provided to the reception
counter to allow approach by all
potential users both seated and
standing.
Provide two work surface heights (dual height worktops) to
accommodate customers or visitors standing and sitting (including
wheelchair users), as appropriate to the circumstance Refer to
BS8300:2001 Section 11.1.3/6 & figure 33 (& Provide an induction loop
or other form of hearing enhancement system. Refer to BS8300:2001
Section 9.3.2)
Complete
Certek House
(Rehabilitation
Ground
Floor
An induction loop is not provided to
assist the hearing impaired with
Provide an induction loop or other form of hearing enhancement
system. Refer to BS8300:2001 Section 9.3.2
Complete
Last updated:
October 2008
Clinic)
communication at staff meetings - A
Large conference room not suitable for
hearing impaired
Councillor Lane
(Cheadle)
Ground
Floor
Non DDA compliant door access -
Excessive force (over 20N) required to
open door which can obstruct some
ambulant disabled persons, wheelchair
users and the elderly.
Adjust door closer to provide 20N maximum resistance. Refer to
BS8300:2001 section 6.3.2. (Automatic Doors Opening Mechanism)
Complete
Ashley Street
Clinic
(Dukinfield)
Ground
Floor
Non DDA Compliant Toilet in Clinic
waiting area– Must provide sanitary
fittings and aids, such as toilet seats
and grab rails that contrast in terms of
colour and luminance with background
wall and floor finishes. Refer to
BS8300:2001 Section 12.4.11
Provide a lavatory suitable for use by ambulant people adjacent to
waiting area. Refer to BS8300:2001 Redecorate walls to highlight
fittings or alternatively colour contrasting bands (stickers) could be
used as an interim measure to highlight the fittings, Refer to
BS8300:2001
Complete
Ashley Street
Clinic
(Dukinfield)
External
Carpark
A designated setting-down
point/accessible parking bay is not
provided close to the principal
entrance of the building.
Provide a designated setting-down point/accessible parking bay
suitable for disabled passengers on firm and level ground, close to the
principal or alternative, accessible entrance to a building. Refer to
BS8300:2001 Section 4.2
Complete
Woods Hospital
(Woods)
External
Carpark
A designated setting-down
point/accessible parking bay is not
provided close to the principal
entrance of the building.
Provide a designated setting-down point/accessible parking bay
suitable for disabled passengers on firm and level ground, close to the
principal or alternative, accessible entrance to a building. Refer to
BS8300:2001 Section 4.2
Complete
Last updated:
October 2008